GL-227TM Extinguishing Agent for Total Flooding Applications
GL-227TM is a gaseous extinguishing
agent, which can be used as a replacement for Halon 1301 in
total flooding systems to protect “normally occupied”
areas.
GL-227 is efficient on Class A, B and C fires, it is
electrically no-conductive and leaves no residue after
discharge.
Halogenated extinguishing agents, when in contact with fires
or burning surfaces, generate dcomposition byproducts, which
can be harmful to humans. In order to limit the creation of
toxic byproducts, GL-227 fire frotection systems are designed
with a maximum discharge time of 10 seconds. The addition of
isoprpenyl l-methyl cyclohexene further reduces the creation
of toxic fumes.
HIGHLIGHTS
Due to its low toxicity level, GL-227 is suitable for
protection of “normally occupied” areas. For most common
applications, the recommended design concentration is lower
than that which would cause harmful effects to the personel
present in the protected area.
The minimum extinguishing concentration for n-heptane,
determined by the cup-burner test, is 6.6% by weight.
The physical properties of GL-227 allow a fast and
homogeneous distribution in the protected volume, ensuring a
rapid and efficient extinguishment of the fire at normal
ambient temperatures.
Use
GL-227 complies with the
requirements of purity for HFC 227 ea as listed in
international standards for gaseous extinguishing agents.
Although any potential fire risk presents its own particular
complexities, the choice of GL-227 in a fire protection
system is suitable when:
· an electrial no-conductive gaseous extinguishing agent is
required
· the clean-up of another media would represent a problem
· the relationship between space/weight and extinguishing
capability is of essence
· the safety of personnel within the protected area must be
guanteed.
Typical examples of hazards where the use of GL-227 is
suitable are: computer rooms, control rooms, archives,
flammable liquid stores, laboratories, military vehicles,
telecommunications system.
Environmental
impact
The Montreal Protocol, which
establishes the actions to control emissions of substances
damaging the ozone layer, banned the manufacture of Halons
due to their high Ozone Depletion Potential (ODP). GL-227,
unlike Halon 1301 (ODP = 12-16), does not contain Bromine
nor Chlorine.
Consequently, it does not deplete the stratospheric ozone
layer (ODP = 0). Also the low Global Warming Potential (GWP)
and low Atmospheric Lifetime (ALT) make it an acceptable
replacement.
Toxicity
GL-227 does not pose any
risk to humans when used at its recommended desing
concentration.
GL-227 acute toxicity (LC50 for 15 minutes = >80%) is far
higher than the normal concentrations of use. Exposure at
lower concentrations for a limited period of time does not
represent a risk to personnel.
Nevertheless, like Halon 1301, exposure to the product at
higher concentrations and for longer periods of time can
cause indisposition, lack of coordination and heart
arrhythmia.
The cardiac sensitization is the first evident symptom when
exposed to halogenated extinguishing agents. The NOAEL (No
Observable Adverse Effect Level) and LOAEL (Lowest Observed
Adverse Effect Level) values for GL-227TM are respectively
9.5% and 10.5%.
GL-125 Physical
Properties
1301
HFC-23
Halon 1301
Molecular
weight
70.01
148.93
Boiling
point @ 1 atm (°C)
-
82.2
-
57.8
Critical
temperature (°C)
25.9
67
Critical
Pressure (bar)
48.36
39.6
Critical
density (Kg./m3)
525
745
Vapour
pressure @ 25°C (bar)
47.29
16.20
Liquid
density @ 25°C (g/ml)
0.67
1.57
Freezing
point (°C)
-155.2
-168
Specific
heat of liquid @ 25°C (j/Kg °C)
1,549
910
Heat
of vapourization at boiling point point (Kj/Kg)
Gielle Srl - Establecimiento y Oficina Via R. Ferri 32 Z.I. - 70022 Altamura (Ba) Italy
Tel +39 0803118998 - Fax + 39 0803101309